Model Door
Wdt.
Inches
Door
Hgt.
Feet
Air Velocity
FPM
@Nozzle
Air Volume
CFM
@Nozzle
Full Load
1 Phase
208/230v
(Note:1)
Amps
3 Phase
480v
(Note:2)
Motor
Horse
Power
Sound
Pressure
Level
(Note:3)
Net Wt.
Lbs
(unheated)
Electric
Heat
available
(Notes:4&5)
WHISPURR AIR MODELS --- --- --- 1550RPM --- --- ---
WA 36 36 up to 7 1800 900 0.8 NA 1@1/6 49 16 X
WA 42 42 up to 7 1800 1050 0.9 NA 1@1/6 50 19 X
WA 48 48 up to 7 1800 1200 1.0 NA 1@1/6 52 22 X
WA 60 60 up to 7 1800 1500 1.1 NA 1@1/4 52 25 X
WA 72 72 up to 7 1800 1800 1.2 NA 1@1/4 53 28 X
Model Door
Wdt.
Inches
Door
Hgt.
Feet
Air Velocity
FPM
@Nozzle
Air Volume
CFM
@Nozzle
Full Load
1 Phase
208/230v
(Note:1)
Amps
3 Phase
480v
(Note:2)
Motor
Horse
Power
Sound
Pressure
Level
(Note:3)
Net Wt.
Lbs
(unheated)
Electric
Heat
available
(Notes:4&5)
C MODELS --- --- --- 1750 RPM --- --- ---
36C 36 UP TO 8 2275 1700 2.5 0.6 1@1/2 56 50 X
38C 38 UP TO 8 2150 1700 2.5 0.6 1@1/2 56 52 X
42C 42 UP TO 8 1950 1700 2.5 0.6 1@1/2 56 55 X
48C 48 UP TO 8 1700 1700 2.5 0.6 1@1/2 56 60 X
60C 60 UP TO 8 2040 2550 2.5 0.6 1@1/2 56 65 X
60C-2 60 UP TO 8 2720 3400 5.1 1.2 2@1/2 63 95 X
72C 72 UP TO 8 2275 3400 5.1 1.2 2@1/2 63 105 X
96C 96 UP TO 8 1700 3400 5.1 1.2 2@1/2 63 130 X
Model Door
Wdt.
Inches
Door
Hgt.
Feet
Air Velocity
FPM
@Nozzle
Air Volume
CFM
@Nozzle
Full Load
1 Phase
208/230v
(Note:1)
Amps
3 Phase
480v
(Note:2)
Motor
Horse
Power
Sound
Pressure
Level
(Note:3)
Net Wt.
Lbs
(unheated)
Electric
Heat
available
(Notes:4&5)
CH MODELS --- --- --- 1750 RPM --- --- ---
36CH 36 8-10 3400 2550 2.5 0.6 1@1/2 63 50 X
38CH 38 8-10 3225 2550 2.5 0.6 1@1/2 63 52 X
42CH 42 8-10 2925 2550 2.5 0.6 1@1/2 63 55 X
48CH 48 8-10 2550 2550 2.5 0.6 1@1/2 63 60 X
60CH-2 60 8-10 4080 5100 5.1 1.2 2@1/2 65 95 X
72CH 72 8-10 3400 5100 5.1 1.2 2@1/2 65 105 X
96CH 96 8-10 2550 5100 5.1 1.2 2@1/2 65 130 X
Model Door
Wdt.
Inches
Door
Hgt.
Feet
Air Velocity
FPM
@Nozzle
Air Volume
CFM
@Nozzle
Full Load
1 Phase
208/230v
(Note:1)
Amps
3 Phase
480v
(Note:2)
Motor
Horse
Power
Sound
Pressure
Level
(Note:3)
Net Wt.
Lbs
(unheated)
Electric
Heat
available
(Notes:4&5)
CHS MODELS --- --- --- 1750 RPM --- --- ---
42CHS 42 10-12 4600 4000 8.0 2.0 1@1 69 80 X
48CHS 48 10-12 4000 4000 8.0 2.0 1@1 69 85 X
60CHS 60 10-12 3200 4000 8.0 2.0 1@1 69 90 X
96CHS 96 10-12 4000 8000 16.0 4.0 2@1 72 160 X
COMBI MODELS --- --- --- 1750RPM --- --- ---
36COMBI 36 UP TO 10 3400/2275 2550/1700 2.5 NA 1@1/2 56/63 50 NA
38COMBI 83 UP TO 10 3225/2150 2550/1700 2.5 NA 1@1/2 56/63 52 NA
42COMBI 42 UP TO 10 2925/1950 2550/1700 2.5 NA 1@1/2 56/63 55 NA
48COMBI 48 UP TO 10 2550/1700 2550/1700 2.5 NA 1@1/2 56/63 60 NA
60COMBI 60 UP TO 10 2040/1360 2550/1700 2.5 NA 1@1/2 56/63 65 NA
60-2COMBI 60 UP TO 10 4080/2720 5100/3400 5.1 NA 2@1/2 59/65 95 NA
72COMBI 72 UP TO 10 3400/2275 5100/3400 5.1 NA 2@1/2 59/65 105 NA
96COMBI 96 UP TO 10 2550/1700 5100/3400 5.1 NA 2@1/2 59/65 130 NA
Model Door
Wdt.
Inches
Door
Hgt.
Feet
Air Velocity
FPM
@Nozzle
Air Volume
CFM
@Nozzle
Full Load
1 Phase
208/230v
(Note:1)
Amps
3 Phase
480v
(Note:2)
Motor
Horse
Power
Sound
Pressure
Level
(Note:3)
Net Wt.
Lbs
(unheated)
Electric
Heat
available
(Notes:4&5)
SUPER COMBI (S/C) MODELS --- --- --- 1750 RPM --- --- ---
42(S/C) 42 10-12 4600/3200 4000/2800 8.0 NA 1@1 65/69 80 NA
48(S/C) 48 10-12 4000/2800 4000/2800 8.0 NA 1@1 65/69 85 NA
60(S/C) 60 10-12 3200/2240 4000/2800 8.0 NA 1@1 65/69 90 NA
96(S/C) 96 10-12 4000/2800 8000/5600 16.0 NA 2@1 68/72 160 NA
NATIONAL SANITATION
FOUNDATION MODELS
--- 1750RPM --- --- ---
36 NCH 36 UP TO 7 3400 2550 2.5 0.6 1@1/2 63 50 NA
38 NCH 38 UP TO 7 3225 2550 2.5 0.6 1@1/2 63 52 NA
42 NCH 42 UP TO 7 2925 2550 2.5 0.6 1@1/2 63 55 NA
48 NCH 48 UP TO 7 2550 2550 2.5 0.6 1@1/2 63 60 NA
72 NCH 72 UP TO 7 3400 5100 5.1 1.2 2@1/2 65 105 NA
NHV 42 42 UP TO 7 4600 4000 8.0 2.0 1@1 69 80 NA
NHV 48 48 UP TO 7 4000 4000 8.0 2.0 1@1 69 85 NA
SERVICE WINDOW
MODEL W-25
--- --- --- 3450 RPM --- --- ---
W25 30 UP TO 5 1400 1900 0.5 NA 1@1/2 59 20 X
HEPAC --- --- --- 1750 RPM --- --- ---
HF-40 40 UP TO 8 2175 1800 2.5 0.6 1@1/2 56 125 NA

NOTES:

1) Single phase full load current for 208/230v shown; for 115v single phase, multiply by 2. For ampacity multiply current by 1.25. 3) The dBA is measured in free air 10 feet from the nozzle.
2) Three phase full load current for 480v shown; for 208/230v three phase, multiply by 2. For ampacity multiply current by 1.25. 4) Heat not available with 115v, single phase air curtains.
5) Commercial Models available in Electric Heat Only
General Notes: Specify voltage and phase when ordering. Electric motors are available in any other voltages, phases and frequencies.

 